Motor Horsepower, Current, and Efficiency
Translate mechanical hp to electrical input current with explicit power factor and efficiency.
Shaft vs electrical power
Motor nameplates may list hp output, full-load amps, and efficiency. Running current tools use shaft power converted to watts before applying √3 V PF η.
Starting current requires a separate multiplier or manufacturer curve — not the running-current page.
Worked example and interpretation
For 50 mechanical hp, shaft output is 37.285 kW. With efficiency 0.92, input real power is about 40.527 kW. At 480 V three-phase and PF 0.85, line current is 50 × 745.6998716/(√3 × 480 × 0.85 × 0.92) = 57.35 A.
Compare a calculated running-current estimate with the actual nameplate at the stated operating point; use manufacturer starting data separately.
Application limits
Use efficiency only when converting shaft output to input power. This does not establish locked-rotor current, motor-table FLA, starting duty or conductor protection.
Related calculators
FAQ
Is mechanical hp the same as electrical kW input?
No. Divide shaft power by efficiency to estimate electrical input under your assumptions.
References
- Guide for the Use of the International System of Units (SI), Appendix B.8 — International length, mechanical horsepower and customary area factors; SI conversion basis. Conversion factors only; legacy source ID is retained and does not denote a 2024 edition. Use separate temperature-interval and absolute-temperature formulas. (verified)