AWG, kcmil, and mm² Explained
Translate wire size names used in US drawings and metric specifications. Nominal areas are not ampacity approvals.
American Wire Gauge
Larger AWG numbers denote smaller nominal conductors. Beyond 1 AWG, the 1/0 through 4/0 designations increase conductor size. Gauge geometry alone does not determine ampacity.
Use the wire size converter for nominal cross-section in mm² and kcmil.
kcmil and circular mil
Large conductors use kcmil (thousands of circular mils). 250 kcmil is a common class size in US distribution drawings.
Insulated outside diameters for conduit fill differ from AWG metal area — enter manufacturer diameters in the physical conduit tool.
Worked example and interpretation
12 AWG follows d = 0.127 × 92^((36−12)/39) mm and A = πd²/4, giving about 3.308773 mm². A custom 250 kcmil area is about 126.676870 mm². AWG 1/0, 2/0, 3/0 and 4/0 correspond to n = 0, −1, −2 and −3.
Use the converter to communicate nominal geometry, then obtain the actual product outside diameter and ratings from its manufacturer.
Application limits
AWG numbers decrease as nominal diameter increases; 4/0 is larger than 1 AWG. Nominal metal area is not insulation diameter or ampacity. An adjacent metric size is not an approved substitute.
Related calculators
Related guides
FAQ
Can I substitute metric cable using only AWG conversion?
Area conversion helps communication; ampacity, temperature, and installation rules still come from your adopted code document.
References
- Copper Wire Tables, Circular of the Bureau of Standards No. 31 — AWG endpoints and 39-step diameter progression; nominal area derived from circular geometry. Bare nominal geometry only; no insulation diameter, ampacity or substitution approval. Circular-mil area is derived using the mil length definition. (verified)
- Guide for the Use of the International System of Units (SI), Appendix B.8 — International length, mechanical horsepower and customary area factors; SI conversion basis. Conversion factors only; legacy source ID is retained and does not denote a 2024 edition. Use separate temperature-interval and absolute-temperature formulas. (verified)