AWG / mm² / kcmil Converter
Convert nominal bare-conductor size between AWG, mm², circular mils and kcmil. Compare the closest AWG and the adjacent smaller and larger nominal areas.
Overview
Convert nominal bare-conductor size between AWG, mm², circular mils and kcmil. Compare the closest AWG and the adjacent smaller and larger nominal areas.
How to Use
Choose the input size representation, then enter an AWG designation or numeric area. Switching between area units converts the existing quantity; switching to AWG retains the nominal area as a custom value until a gauge is explicitly selected. Reset restores the initial example.
Input Units
AWG 40 through 1, plus 1/0 through 4/0; mm²; circular mils; and custom positive kcmil. One circular mil is approximately 0.0005067074791 mm².
Formula and Variable Definitions
dmm=0.127 × 92^((36−n)/39); Amm²=πdmm²/4; 1 cmil=π(0.0254 mm)²/4
n is the AWG number, with 1/0=0, 2/0=−1, 3/0=−2 and 4/0=−3. d is nominal solid round-conductor diameter; A is nominal conductor area.
Worked Example
Enter 12 AWG. Nominal area is approximately 3.308773 mm², or 6.529947 kcmil. For a custom 3.5 mm² area, 12 AWG is nearest and smaller; 11 AWG is the adjacent larger nominal area.
Understanding the Results
The nearest AWG minimizes the absolute nominal area difference. Smaller and larger refer to nominal area; AWG numbers run in the opposite direction. Outside the supported AWG range, an adjacent size may be unavailable.
Practical Applications
Read manufacturer conductor specifications, compare nominal area conventions and convert a user supplied kcmil value to SI area.
Common Mistakes
Do not confuse mil diameter with circular-mil area, 1/0 AWG with 1 AWG, or nominal conductor diameter with insulated cable diameter.
Limitations
Nominal area is not stranded outside diameter, insulation diameter, ampacity or conduit occupancy. Nearby nominal areas do not establish electrical or regulatory interchangeability. No NEC tables or cable products are selected.
FAQ
What does kcmil mean?
One kcmil is 1,000 circular mils. A circular mil is the area of a circle one thousandth of an inch in diameter.
Is there always an exact AWG equivalent?
No. AWG is discrete. The converter distinguishes nearest nominal area from the adjacent smaller and larger sizes.
What are the limitations?
Nominal area is not stranded outside diameter, insulation diameter, ampacity or conduit occupancy. Nearby nominal areas do not establish electrical or regulatory interchangeability. No NEC tables or cable products are selected.
Related Calculators
References
NBS Circular 31, second edition, AWG geometric definition. Unit factors: NIST SP 811 Appendix B.8.