Conduit Fill Calculation (Physical Areas)
Sum insulated conductor areas against raceway area — a Type 1 check before you apply allowable fill from your code book.
Physical vs code allowances
Percent fill equals total insulated area divided by raceway internal area. Allowable percentages for one, two, or many conductors come from your NEC edition if licensed for your use.
This site does not store Chapter 9 table diameters.
Worked example and interpretation
Three insulated cables of 3.31 mm² outside cross-sectional area and one of 5.26 mm² occupy 15.19 mm². In a raceway with 178 mm² internal area, the physical fraction is 15.19/178 × 100 = 8.5337%. These are illustrative outside areas, not bare AWG areas.
Keep a geometric occupancy number separate from an allowable percentage. A small calculated fraction is not a compliance verdict.
Application limits
Use product insulated outside area and raceway internal area. The percentage is geometry only; permitted fill, pulling requirements and conductor count rules require independently verified project criteria.
Related calculators
Related guides
FAQ
Can I use bare AWG area for fill?
No. Use manufacturer insulated cross-section or measured OD-based area.
References
- Explicit mathematical definitions used by Ampory — Ratios, sums, differences, area fractions and user-defined scheduling arithmetic. Pure arithmetic is independently checked; this is not external technical or regulatory approval. (pending)
- Guide for the Use of the International System of Units (SI), Appendix B.8 — International length, mechanical horsepower and customary area factors; SI conversion basis. Conversion factors only; legacy source ID is retained and does not denote a 2024 edition. Use separate temperature-interval and absolute-temperature formulas. (verified)