Skip to content
AMPORYUnited States

Conductors

Busbar review

Calculate total rectangular busbar metal area, current density and an optional user-supplied current-density comparison.

Not a standard ampacity table.

Enter values and press Calculate to see results here.

Calculator overview

Calculate total rectangular busbar metal area, current density and an optional user-supplied current-density comparison.

How to use

  1. Enter bar width and thickness in mm and the number of parallel bars.
  2. Enter total current.
  3. Read combined area and average current density. Optional short-circuit current and duration give an arithmetic I²t value.

Formula

A = w t n, J = I/A, I²t = Isc² t

  • J (A/mm²) — See the Formula section and worked example for calculation steps.

Worked example

Worked example: busbar

Inputs: current = 800, width = 100, thickness = 10, bars = 1. J = I/(width × thickness × bars); no resistance model. Expected j = 0.8 A/mm². Display precision may round this value.

Expect key result j to contain 0.8 when you run the calculator with the same inputs.

Understanding the results

Area is width × thickness × bar count. Average density is total current divided by that area. This tool has no material, length or temperature input and does not calculate resistance or voltage drop.

Practical applications

Switchgear preliminary checks, IR survey follow-ups.

Common mistakes

Ignoring joint resistance and temperature rise limits.

Limitations

Average geometry/current-density arithmetic does not predict temperature rise, skin/proximity effects, mechanical forces or manufacturer thermal/short-circuit acceptance.

Results are engineering estimates only. They are not NEC compliance, arc-flash studies, or licensed design deliverables.

References

FAQ

Aluminum versus copper?
Select material—resistivity changes R for the same size.
AC vs DC drop?
Follow form—reactance may be omitted for short bus sections.
Multiple bars in parallel?
Use cable-parallel concepts or model each run separately.