User-Supplied Ampacity Check
Implementation: TYPE2 USER SUPPLIED
Multiply a user-supplied table ampacity and correction factors, then compare with your design current. The site does not ship NEC Table 310.16.
Overview
Multiply a user-supplied table ampacity and correction factors, then compare with your design current. The site does not ship NEC Table 310.16.
How to Use
Enter values from your one-line diagram, nameplate or code tables you already verified. Calculate, then compare with manufacturer or engineering documents.
Formula
Iz′ = Iz × kθ × k_group × k_other; review Ib ≤ Iz′
Worked Example
Continuous load current Ib: 92 A; Tabulated ampacity Iz from your document: 110 A; Temperature correction factor: 0.94 factor; Bundling correction factor: 0.8 factor; Other correction factor: 1 factor. Primary result (izp) ≈ 82.72 A.
Applicable Conditions
Document a comparison after you look up an ampacity table yourself.
Code and Jurisdiction Notes
Type 2 only. NFPA NEC table text is not embedded (BLOCKED_LICENSE).
Limitations
You must obtain Iz and factors from the NEC edition adopted by your AHJ or manufacturer data.
FAQ
Is this NEC compliant?
No. This is an engineering or user-documented check only. Your AHJ and adopted code edition govern compliance.
Where do code tables come from?
User-supplied tools require values from your NEC adopted edition, manufacturer data, or utility. This site does not embed NFPA tables.
What are the limitations?
You must obtain Iz and factors from the NEC edition adopted by your AHJ or manufacturer data.