User-Supplied Ampacity Check

Implementation: TYPE2 USER SUPPLIED

Multiply a user-supplied table ampacity and correction factors, then compare with your design current. The site does not ship NEC Table 310.16.

Overview

Multiply a user-supplied table ampacity and correction factors, then compare with your design current. The site does not ship NEC Table 310.16.

How to Use

Enter values from your one-line diagram, nameplate or code tables you already verified. Calculate, then compare with manufacturer or engineering documents.

Formula

Iz′ = Iz × kθ × k_group × k_other; review Ib ≤ Iz′

Worked Example

Continuous load current Ib: 92 A; Tabulated ampacity Iz from your document: 110 A; Temperature correction factor: 0.94 factor; Bundling correction factor: 0.8 factor; Other correction factor: 1 factor. Primary result (izp) ≈ 82.72 A.

Applicable Conditions

Document a comparison after you look up an ampacity table yourself.

Code and Jurisdiction Notes

Type 2 only. NFPA NEC table text is not embedded (BLOCKED_LICENSE).

Limitations

You must obtain Iz and factors from the NEC edition adopted by your AHJ or manufacturer data.

FAQ

Is this NEC compliant?

No. This is an engineering or user-documented check only. Your AHJ and adopted code edition govern compliance.

Where do code tables come from?

User-supplied tools require values from your NEC adopted edition, manufacturer data, or utility. This site does not embed NFPA tables.

What are the limitations?

You must obtain Iz and factors from the NEC edition adopted by your AHJ or manufacturer data.