Motors
Motor slip and synchronous speed
Relates synchronous speed, measured rpm, and slip for induction machines.
Calculator overview
Relates synchronous speed, measured rpm, and slip for induction machines.
How to use
- Enter poles and line frequency (60 Hz typical in the US).
- Enter measured or rated rpm.
- Read synchronous speed and slip percent.
- Compare to nameplate full-load slip when loaded.
- Use with motor current tools for context.
Formula
Ns = 120 f / P, s = (Ns − Nr) / Ns × 100
- f (Hz) — Frequency
- P (—) — 2, 4, 6, 8, 10, 12
- Ns (r/min) — See the Formula section and worked example for calculation steps.
- Nr (r/min) — See the Formula section and worked example for calculation steps.
- s (%) — See the Formula section and worked example for calculation steps.
Worked example
Worked example: motor slip
Inputs: calcMode = from-rpm, poles = 4, freqPreset = 60, rpm = 1750. Ns = 120f/poles; s = (Ns−Nr)/Ns × 100. Expected slip = 2.777778 %. Display precision may round this value.
Expect key result slip to contain 2.777778 when you run the calculator with the same inputs.
Understanding the results
Slip increases with mechanical load; no-load rpm is nearer synchronous speed.
Practical applications
Post-VFD rpm checks, mechanical troubleshooting, training.
Common mistakes
Using 50 Hz on US 60 Hz systems without updating frequency.
Limitations
No torque or current estimation.
Results are engineering estimates only. They are not NEC compliance, arc-flash studies, or licensed design deliverables.
References
- Guide for the Use of the International System of Units (SI), Appendix B.8(verified)
International length, mechanical horsepower and customary area factors; SI conversion basis. Conversion factors only; legacy source ID is retained and does not denote a 2024 edition. Use separate temperature-interval and absolute-temperature formulas.
- DOE Fundamentals Handbook, Electrical Science Volume 4(verified)
Synchronous speed and slip; ideal transformer ratios and output/input efficiency. Ideal or simplified steady-state relationships; no instrument transformer burden class, insulation rating or parallel-operation approval.
FAQ
- Why can't an induction motor hit synchronous speed?
- Torque requires slip in the rotor circuit.
- Pole count source?
- Use the motor nameplate pole count.
- High slip at rated load?
- May indicate overload, voltage depression, or mechanical drag—investigate further.