Transformers
Transformer rated current
Calculates three-phase rated line currents on primary and secondary sides from nameplate kVA and line-to-line voltages: I = S / (√3 × V). Results support cable sizing discussions, metering CT planning, and procurement checks—they are not short-circuit duty, tap-compensated protection, or substation relay settings.
Calculator overview
Calculates three-phase rated line currents on primary and secondary sides from nameplate kVA and line-to-line voltages: I = S / (√3 × V). Results support cable sizing discussions, metering CT planning, and procurement checks—they are not short-circuit duty, tap-compensated protection, or substation relay settings.
How to use
- Enter rated kVA from the transformer nameplate at the tap you are analyzing.
- Enter primary and secondary line-to-line voltages (e.g., 12.47 kV / 480 V distribution transformers).
- Leave unused voltage fields empty only if the form allows one-sided calculations.
- Compare I₁ and I₂—secondary current rises when voltage is lower for the same kVA.
- Cross-check with utility meter CT ranges before procurement; use short-circuit tools for fault studies.
- Document that these are full-load rated currents, not energization inrush or through-fault withstand.
Formula
I = S / (√3 V)
- S (kVA) — Apparent power
Worked example
Worked example: transformer current
Inputs: ratedKva = 750, vPrimary = 12470, vPrimaryUnit = V, vSecondary = 480, vSecondaryUnit = V. I2 = S/(√3 V2LL). Expected i2 = 902.109796 A. Display precision may round this value.
Expect key result i2 to contain 902.109796 when you run the calculator with the same inputs.
Understanding the results
At a common three-phase kVA base, primary and secondary line currents scale inversely with their line-to-line voltages. This tool requires both voltages and always uses the balanced three-phase √3 relationship; it has no single-phase mode.
Practical applications
Sizing secondary mains and switchboards, picking CT primary amps above normal FLA, comparing two transformer proposals, teaching interns how 480 V services produce high secondary currents on medium-size kVA units.
Common mistakes
Using phase-to-neutral 277 V in the √3 line formula without adjusting, applying secondary current formulas to primary voltage by mistake, confusing rated current with maximum fault current, and ignoring parallel transformers or load diversity.
Limitations
No %Z, tap changer, fan rating, coaxial harmonics, or dual-voltage winding series/parallel reconnection. Does not determine protective device interrupting duty.
Results are engineering estimates only. They are not NEC compliance, arc-flash studies, or licensed design deliverables.
References
- Guide for the Use of the International System of Units (SI), Appendix B.8(verified)
International length, mechanical horsepower and customary area factors; SI conversion basis. Conversion factors only; legacy source ID is retained and does not denote a 2024 edition. Use separate temperature-interval and absolute-temperature formulas.
- University Physics Volume 2, 15.4 Power in an AC Circuit(verified)
Sinusoidal RMS real power P=VI cosφ; resistor I²R loss. Single-phase sinusoidal AC; this section does not itself establish three-phase √3 relations.
- DOE Fundamentals Handbook, Electrical Science Volume 3(verified)
RMS P/Q/S relationships and balanced line-voltage/current power relations. Balanced sinusoidal fundamentals; efficiency conversion and user margins are explicit algebraic assumptions, not equipment selection standards.
FAQ
- Why is secondary current so high at 480 V?
- At fixed kVA, current rises as voltage drops because S = √3 V I.
- Which voltage should I enter for a 480Y/277 V secondary?
- Use line-to-line 480 V for standard three-phase line-current formulas in this tool.
- Do these numbers size breakers?
- They are rated full-load values; overcurrent rules and inrush need separate engineering.
- How do I check a padmount nameplate?
- Match kVA and voltages at the active tap, then compare computed amps to the nameplate FLA if printed.
- Are primary currents used for relaying?
- Relay CT ratios start from these FLA ideas but require system studies—not this calculator alone.