Transformer rated current

Calculates three-phase rated line currents on primary and secondary sides from nameplate kVA and line-to-line voltages: I = S / (√3 × V). Results support cable sizing discussions, metering CT planning, and procurement checks—they are not short-circuit duty, tap-compensated protection, or substation relay settings.

Nameplate kVA at rated taps; not short-circuit duty.

Enter values and press Calculate to see results here.

Calculator overview

Calculates three-phase rated line currents on primary and secondary sides from nameplate kVA and line-to-line voltages: I = S / (√3 × V). Results support cable sizing discussions, metering CT planning, and procurement checks—they are not short-circuit duty, tap-compensated protection, or substation relay settings.

How to use

  1. Enter rated kVA from the transformer nameplate at the tap you are analyzing.
  2. Enter primary and secondary line-to-line voltages (e.g., 12.47 kV / 480 V distribution transformers).
  3. Leave unused voltage fields empty only if the form allows one-sided calculations.
  4. Compare I₁ and I₂—secondary current rises when voltage is lower for the same kVA.
  5. Cross-check with utility meter CT ranges before procurement; use short-circuit tools for fault studies.
  6. Document that these are full-load rated currents, not energization inrush or through-fault withstand.

Formula

I = S / (√3 V)

  • S (kVA) — Apparent power

Worked example

Worked example: transformer current

Inputs: ratedKva = 750, vPrimary = 12470, vPrimaryUnit = V, vSecondary = 480, vSecondaryUnit = V. I2 = S/(√3 V2LL). Expected i2 = 902.109796 A. Display precision may round this value.

Expect key result i2 to contain 902.109796 when you run the calculator with the same inputs.

Understanding the results

At a common three-phase kVA base, primary and secondary line currents scale inversely with their line-to-line voltages. This tool requires both voltages and always uses the balanced three-phase √3 relationship; it has no single-phase mode.

Practical applications

Sizing secondary mains and switchboards, picking CT primary amps above normal FLA, comparing two transformer proposals, teaching interns how 480 V services produce high secondary currents on medium-size kVA units.

Common mistakes

Using phase-to-neutral 277 V in the √3 line formula without adjusting, applying secondary current formulas to primary voltage by mistake, confusing rated current with maximum fault current, and ignoring parallel transformers or load diversity.

Limitations

No %Z, tap changer, fan rating, coaxial harmonics, or dual-voltage winding series/parallel reconnection. Does not determine protective device interrupting duty.

Results are engineering estimates only. They are not NEC compliance, arc-flash studies, or licensed design deliverables.

References

FAQ

Why is secondary current so high at 480 V?
At fixed kVA, current rises as voltage drops because S = √3 V I.
Which voltage should I enter for a 480Y/277 V secondary?
Use line-to-line 480 V for standard three-phase line-current formulas in this tool.
Do these numbers size breakers?
They are rated full-load values; overcurrent rules and inrush need separate engineering.
How do I check a padmount nameplate?
Match kVA and voltages at the active tap, then compare computed amps to the nameplate FLA if printed.
Are primary currents used for relaying?
Relay CT ratios start from these FLA ideas but require system studies—not this calculator alone.