Transformers
Transformer losses
Estimates no-load and load losses and efficiency from nameplate loss data and loading.
Calculator overview
Estimates no-load and load losses and efficiency from nameplate loss data and loading.
How to use
- Enter rated kVA, no-load loss and full-load loss in kW from a test report.
- Enter actual operating load in kVA and its power factor.
- Read total loss, loading fraction and estimated efficiency.
Formula
P_loss = P0 + Pk β², η = Pout/(Pout+Ploss)
- β (pu) — S/Srated
Worked example
Worked example: transformer loss
Inputs: ratedKva = 500, noLoadKw = 1, loadLossKw = 6, loadKva = 250, pf = 0.9. Ploss = P0 + Pk (Sload/Srated)². Expected ploss = 2.5 kW. Display precision may round this value.
Expect key result ploss to contain 2.5 when you run the calculator with the same inputs.
Understanding the results
Load fraction β is actual load kVA divided by rated kVA. Total loss is P0+Pkβ²; output real power is load kVA times PF. Temperature and harmonic stray losses are not separately modeled.
Practical applications
Energy audits, transformer replacement studies.
Common mistakes
Using obsolete nameplate losses after rewinds or retrofits.
Limitations
No harmonic stray loss model.
Results are engineering estimates only. They are not NEC compliance, arc-flash studies, or licensed design deliverables.
References
- Guide for the Use of the International System of Units (SI), Appendix B.8(verified)
International length, mechanical horsepower and customary area factors; SI conversion basis. Conversion factors only; legacy source ID is retained and does not denote a 2024 edition. Use separate temperature-interval and absolute-temperature formulas.
- University Physics Volume 2, 9.5 Electrical Energy and Power(verified)
P=IV; resistor dissipation; energy as power integrated over time. DC/resistive and ideal energy accounting; efficiency and capacity factors are user assumptions, not battery discharge curves.
- DOE Fundamentals Handbook, Electrical Science Volume 3(verified)
RMS P/Q/S relationships and balanced line-voltage/current power relations. Balanced sinusoidal fundamentals; efficiency conversion and user margins are explicit algebraic assumptions, not equipment selection standards.
- DOE Fundamentals Handbook, Electrical Science Volume 4(verified)
Synchronous speed and slip; ideal transformer ratios and output/input efficiency. Ideal or simplified steady-state relationships; no instrument transformer burden class, insulation rating or parallel-operation approval.
FAQ
- DOE efficiency rules?
- Regulatory classes are outside this physics summary.
- Temperature?
- Losses vary with ambient and loading profile—single-point estimates only.
- Parallel units?
- Losses add per transformer; loading split is not analyzed here.