Electrical fundamentals
kW / kVA / HP converter
Convert a known kW, kVA or horsepower quantity using the supplied power factor and the shared rounded 746 W per mechanical HP convention.
Calculator overview
Convert a known kW, kVA or horsepower quantity using the supplied power factor and the shared rounded 746 W per mechanical HP convention.
How to use
- Choose the known power representation and enter its magnitude.
- Provide power factor for real/apparent power conversion.
- Read kW, kVA, HP and watts for the same power basis.
- For a motor shaft-to-input estimate with efficiency, use Motor Running Current. This converter has no efficiency field.
Formula
kW = kVA × PF, kVA = kW / PF, HP = kW / 0.746
- kW (kW) — Real power
- kVA (kVA) — Apparent power
- PF (—) — kW / kVA
- HP (HP) — See the Formula section and worked example for calculation steps.
Worked example
Worked example: kw kva hp
Inputs: mode = from-hp, hp = 50, pf = 0.86. S = hp × 0.746/PF (legacy rounded horsepower; no efficiency input). Expected kva = 43.372093 kVA. Display precision may round this value.
Expect key result kva to contain 43.372093 when you run the calculator with the same inputs.
Understanding the results
HP uses the 746 W per mechanical horsepower basis in the engine unless the form states otherwise.
Practical applications
Motor nameplate reviews, generator kW/kVA discussions, and inverter sizing prep.
Common mistakes
Treating HP as input kW without efficiency, confusing generator kVA with deliverable kW at low PF.
Limitations
A power-unit conversion does not convert shaft power to electrical input without an efficiency assumption. The legacy shared converter rounds mechanical HP to 746 W; other US tools use the more precise mechanical hp factor. No equipment derating is applied.
Results are engineering estimates only. They are not NEC compliance, arc-flash studies, or licensed design deliverables.
References
- Guide for the Use of the International System of Units (SI), Appendix B.8(verified)
International length, mechanical horsepower and customary area factors; SI conversion basis. Conversion factors only; legacy source ID is retained and does not denote a 2024 edition. Use separate temperature-interval and absolute-temperature formulas.
- DOE Fundamentals Handbook, Electrical Science Volume 3(verified)
RMS P/Q/S relationships and balanced line-voltage/current power relations. Balanced sinusoidal fundamentals; efficiency conversion and user margins are explicit algebraic assumptions, not equipment selection standards.
FAQ
- Why 746 W per HP?
- Mechanical horsepower conversion used in the shared engine—confirm against your nameplate context.
- When is PF required?
- When moving between real (kW) and apparent (kVA) power.
- Does this give line current?
- Pair with a current calculator and system voltage.