Power factor calculator

Computes power factor from kW and kVA or related inputs per the form layout.

Enter values and press Calculate to see results here.

Calculator overview

Computes power factor from kW and kVA or related inputs per the form layout.

How to use

  1. Choose real/apparent-power inputs or the voltage/current mode.
  2. Use kW and kVA for the same circuit and observation period.
  3. In voltage/current mode, choose the actual phase arrangement and use the corresponding voltage basis.
  4. Review P/S, inferred reactive power magnitude and limitations.

Formula

PF = P / S, Q = √(S² − P²), S = √3 × V × I / 1000

  • PF (—) — Power factor
  • P (kW) — Real power
  • S (kVA) — Apparent power
  • Q (kvar) — Reactive power

Worked example

Worked example: power factor

Inputs: mode = from-power, kw = 250, kva = 312. PF = P/S. Expected pf = 0.801282 —. Display precision may round this value.

Expect key result pf to contain 0.801282 when you run the calculator with the same inputs.

Understanding the results

PF is real/apparent for the quantities entered; meters may report displacement vs total PF differently.

Practical applications

Utility penalty reviews, capacitor scoping, before/after correction documentation.

Common mistakes

Mixing time windows, or using single-phase kVA on a three-phase aggregate without care.

Limitations

The triangle estimate assumes consistent sinusoidal quantities. It does not separate harmonic distortion or determine the sign of reactive power from kW/kVA alone.

Results are engineering estimates only. They are not NEC compliance, arc-flash studies, or licensed design deliverables.

References

FAQ

Can PF exceed 1?
Valid inputs keep PF ≤ 1; higher values indicate inconsistent entries.
Leading loads?
Some forms use signed kvar; read leading/lagging notes in the results.
Relation to current?
Lower PF increases line current for the same kW.