Electrical fundamentals
Three-phase load current calculator
Calculates balanced three-phase line current from kW, line-to-line voltage, power factor, and efficiency.
Calculator overview
Calculates balanced three-phase line current from kW, line-to-line voltage, power factor, and efficiency.
How to use
- Enter three-phase real power.
- Use line-to-line voltage (480 V, 208 V, etc.).
- Decimal power factor; typical motors are lagging below 1.
- Use efficiency 1 when kW is already electrical input power.
- Read the primary line current.
Formula
I = P / (√3 × V × PF × η)
- I (A) — Electric current
- P (W) — Real power
- V (V) — Voltage
- PF (—) — Power factor
- η (—) — Efficiency
Worked example
Worked example: three phase current
Inputs: power = 10, powerUnit = kW, voltage = 208, voltageUnit = V, pf = 0.85, efficiency = 0.95. I = P/(√3 VLL PF η). Expected current = 34.374272 A. Display precision may round this value.
Expect key result current to contain 34.374272 when you run the calculator with the same inputs.
Understanding the results
Balanced three-phase line current; phase unbalance and harmonics are not modeled.
Practical applications
Motor feeder sizing conversations, transformer load summaries, and MCC lineup checks.
Common mistakes
Dividing by 3 instead of √3, or using phase voltage in a line-voltage field.
Limitations
Sinusoidal fundamental; not a motor FLA table replacement.
Results are engineering estimates only. They are not NEC compliance, arc-flash studies, or licensed design deliverables.
References
- Guide for the Use of the International System of Units (SI), Appendix B.8(verified)
International length, mechanical horsepower and customary area factors; SI conversion basis. Conversion factors only; legacy source ID is retained and does not denote a 2024 edition. Use separate temperature-interval and absolute-temperature formulas.
- University Physics Volume 2, 15.4 Power in an AC Circuit(verified)
Sinusoidal RMS real power P=VI cosφ; resistor I²R loss. Single-phase sinusoidal AC; this section does not itself establish three-phase √3 relations.
- IEEE Std 141 (Brown Book) — commercial building power(pending)
Voltage system naming 208Y/120, 480Y/277 discussed in industry practice. Full standard not body-verified; guide stays educational
- DOE Fundamentals Handbook, Electrical Science Volume 3(verified)
RMS P/Q/S relationships and balanced line-voltage/current power relations. Balanced sinusoidal fundamentals; efficiency conversion and user margins are explicit algebraic assumptions, not equipment selection standards.
FAQ
- Wye vs delta connection?
- This form uses the standard three-phase kW-to-line-current relationship with line-to-line voltage.
- Can PF be leading?
- Use the PF magnitude for current magnitude in this calculation.
- How is this different from kVA-based current?
- If only kVA is known, use apparent-power forms; this tool starts from real kW.