Electrical fundamentals
Current to power calculator
Estimate real electrical power in kW from line current, load voltage and power factor for a two-wire single-phase or balanced three-phase circuit.
Calculator overview
Estimate real electrical power in kW from line current, load voltage and power factor for a two-wire single-phase or balanced three-phase circuit.
How to use
- Select the actual phase arrangement.
- Enter line current, voltage across the two-wire load or three-phase line-to-line voltage, and power factor.
- Calculate the estimated kW and watts. Use a current calculator for the reverse power-to-current direction.
Formula
Single-phase P = V × I × PF, Three-phase P = √3 × V × I × PF
- P (W) — Real power
- V (V) — Voltage
- I (A) — Electric current
- PF (—) — Power factor
Worked example
Worked example: amp to kw
Inputs: phase = 3, current = 100, voltage = 480, voltageUnit = V, pf = 0.88. P = √3 VLL I PF/1000. Expected kw = 73.161826 kW. Display precision may round this value.
Expect key result kw to contain 73.161826 when you run the calculator with the same inputs.
Understanding the results
The result is real input power for the entered RMS current and power factor. This tool does not switch between forward and reverse conversion modes.
Practical applications
Clamp-meter walkdowns, UPS/generator loading spot checks, and classroom P = √3 V I cos φ drills.
Common mistakes
PF = 1 on mixed induction loads, or line vs phase current confusion on delta circuits.
Limitations
Single snapshot; no interval demand integration.
Results are engineering estimates only. They are not NEC compliance, arc-flash studies, or licensed design deliverables.
References
- Guide for the Use of the International System of Units (SI), Appendix B.8(verified)
International length, mechanical horsepower and customary area factors; SI conversion basis. Conversion factors only; legacy source ID is retained and does not denote a 2024 edition. Use separate temperature-interval and absolute-temperature formulas.
- University Physics Volume 2, 15.4 Power in an AC Circuit(verified)
Sinusoidal RMS real power P=VI cosφ; resistor I²R loss. Single-phase sinusoidal AC; this section does not itself establish three-phase √3 relations.
- DOE Fundamentals Handbook, Electrical Science Volume 3(verified)
RMS P/Q/S relationships and balanced line-voltage/current power relations. Balanced sinusoidal fundamentals; efficiency conversion and user margins are explicit algebraic assumptions, not equipment selection standards.
FAQ
- Is this the same as utility billing kW?
- Billing may use interval demand and metering class rules beyond this formula.
- Do I need both volts and amps?
- Yes—power conversion requires voltage, current, and PF (for AC real power).
- Split-phase 120/240?
- Use the voltage and current definitions that match how you measured the branch.