Single-phase load current calculator

Estimates single-phase line current from real power, voltage, power factor, and optional efficiency. Use for branch load checks and nameplate comparisons—not NEC ampacity selection.

Enter as a decimal (e.g. 0.85), not a percentage.

Advanced inputs

Review inputs, units, and applicable electrical practice — not a code compliance check.

Enter values and press Calculate to see results here.

Calculator overview

Estimates single-phase line current from real power, voltage, power factor, and optional efficiency. Use for branch load checks and nameplate comparisons—not NEC ampacity selection.

How to use

  1. Enter real power in kW or W.
  2. Use the voltage at the load (common North American values include 120 V and 240 V).
  3. Enter power factor as a decimal (0.90), not a percentage.
  4. Set efficiency below 1 only when power is mechanical output.
  5. Compare the primary current (A) to expected full-load current.

Formula

I = P / (V × PF × η)

  • I (A) — Calculated line current
  • P (W) — Load real power
  • V (V) — Line-to-neutral or applied voltage
  • PF (—) — Power factor strictly between 0 and 1
  • η (—) — Motor or drive efficiency; use 1 for resistive loads

Worked example

Worked example: single phase current

Inputs: power = 3, powerUnit = kW, voltage = 120, voltageUnit = V, pf = 0.9, efficiency = 1. I = P/(V PF η). Expected current = 27.777778 A. Display precision may round this value.

Expect key result current to contain 27.777778 when you run the calculator with the same inputs.

Understanding the results

Result is RMS amperes for the PF you supply. Inrush, harmonics, and demand diversity are not included.

Practical applications

Temporary service validation, large heater feeders, and teaching Ohm's-law power relationships on real loads.

Common mistakes

Using 208 V line-to-line on a 120 V neutral load, entering PF as 90, or double-applying efficiency.

Limitations

Physics-only steady-state model. Does not apply utility demand, demand factors, or conductor ampacity tables.

Results are engineering estimates only. They are not NEC compliance, arc-flash studies, or licensed design deliverables.

References

FAQ

When do I use 120 V vs 240 V?
Use the voltage at the equipment terminals for the branch you are analyzing.
Does this show motor LRA?
No—only running current from power and PF.
Why might a clamp meter disagree?
Harmonics, duty cycle, and meter averaging windows differ from a single PF snapshot.