Power factor correction

Estimates kvar and approximate current change to reach a target power factor.

Enter values and press Calculate to see results here.

Calculator overview

Estimates kvar and approximate current change to reach a target power factor.

How to use

  1. Enter constant real power kW.
  2. Enter present and target PF as decimals.
  3. Choose phase and voltage for optional current delta.
  4. Review required kvar.
  5. Engineer switching steps, voltage rating, and detuning separately.

Formula

Qc = P (tanφ1 − tanφ2)

  • P (kW) — Real power
  • φ (rad) — arccos(PF)

Worked example

Worked example: power factor correction

Inputs: powerKw = 45, pfNow = 0.72, pfTarget = 0.90, voltage = 480, phase = 3. Qc = P [√(PF1⁻²−1) − √(PF2⁻²−1)]. Expected qc = 21.578884 kvar. Display precision may round this value.

Expect key result qc to contain 21.578884 when you run the calculator with the same inputs.

Understanding the results

kvar is computed from tan φ differences at the kW you hold constant.

Practical applications

Capacitor bank proposals, loss reduction estimates, utility PF programs.

Common mistakes

Targeting 1.0 PF on varying loads and over-correcting at light load.

Limitations

No harmonic detuning or automatic switching logic.

Results are engineering estimates only. They are not NEC compliance, arc-flash studies, or licensed design deliverables.

References

FAQ

Typical target PF?
Often 0.90–0.95 lagging is discussed with the utility—avoid leading PF at light load.
Capacitor nameplate kvar?
Rated at a specific voltage; apply manufacturer rules when voltage differs.
Harmonics?
Use harmonic-filter and THD tools for distortion mitigation.