Power quality
kW kVAR kVA triangle
Constructs kW–kvar–kVA relationships and phase angle for visualization and field checks.
Calculator overview
Constructs kW–kvar–kVA relationships and phase angle for visualization and field checks.
How to use
- Enter two triangle legs as the form allows (often kW and kvar or kW and kVA).
- Indicate lagging vs leading if prompted.
- Compare sides to analyzer readings.
- Use PF = kW/kVA from results.
- Feed target PF into the correction calculator if needed.
Formula
S² = P² + Q², PF = P/S
- S (kVA) — Apparent power
- P (kW) — Real power
- Q (kvar) — Reactive power
Worked example
Worked example: power triangle
Inputs: mode = pq, kw = 180, kvar = 120. S = √(P²+Q²). Expected s = 216.333077 kVA. Display precision may round this value.
Expect key result s to contain 216.333077 when you run the calculator with the same inputs.
Understanding the results
All legs must share the same measurement interval.
Practical applications
Training, verifying utility bill components, documenting correction proposals.
Common mistakes
Adding kvar without vector sign on leading loads.
Limitations
Single-frequency snapshot; harmonics inflate many meter kVA readings.
Results are engineering estimates only. They are not NEC compliance, arc-flash studies, or licensed design deliverables.
References
- Guide for the Use of the International System of Units (SI), Appendix B.8(verified)
International length, mechanical horsepower and customary area factors; SI conversion basis. Conversion factors only; legacy source ID is retained and does not denote a 2024 edition. Use separate temperature-interval and absolute-temperature formulas.
- University Physics Volume 2, 15.4 Power in an AC Circuit(verified)
Sinusoidal RMS real power P=VI cosφ; resistor I²R loss. Single-phase sinusoidal AC; this section does not itself establish three-phase √3 relations.
- DOE Fundamentals Handbook, Electrical Science Volume 3(verified)
RMS P/Q/S relationships and balanced line-voltage/current power relations. Balanced sinusoidal fundamentals; efficiency conversion and user margins are explicit algebraic assumptions, not equipment selection standards.
FAQ
- Why isn't kVA = kW + kvar?
- Apparent power is vector magnitude, not scalar sum.
- Single-phase ok?
- Yes for the metered segment—keep V/I basis consistent.
- Does this size capacitors?
- Use power-factor-correction for kvar targets.